Earth Leakage Circuit Breaker F Style NV-C Class (Economy Product) Harmonic/Surge Compatible Type NV63-CVF

NV-C Type Earth Leakage Breaker Features

Standard support for mounting IEC 35 mm rail.
Standard compatibility with protection grade IP20 from all directions of terminal area.
Mountable operation handle.
Shunt trip device (SHT) can be mounted on the earth leakage breaker.

NV-C Type Earth Leakage Breaker Specifications

Frame A50
Type NameNV63-CVF
Rated Current in A (*3)
Standard Ambient Temperature 40°C
(5) (10) 15
20 30 40 50
Number of Poles23
Phase Wire Model (*1)1ø2 W3 ø3 W,
1 ø3 W,
1 ø2 W
Rated Operating Voltage Ue V (*2)AC100 to 240100 to 440
High-Speed TypeRated Sensitivity Current mA3030 100
(200)
(500)
Maximum Operating Time sAt IΔn0.1
At 5IΔn0.04
Time Delay TypeRated Sensitivity Current mA-
Maximum Operating Time s (*4)-
Minimum Limiting Non-actuating Time s-
Rated Short Circuit Breaking Capacity
kA
JIS C 8201-2-2 Ann. 1
JIS C 8201-2-2 Ann. 2
IEC 60947-2 2nd. ed.
(Icu/Ics)
(*5)
AC440 V-2.5/2.5
415 V-5/5
400 V-5/5
230 V7.5/7.5
200 V7.5/7.5
100 V7.5/7.5
Rated Impulse Withstand Voltage Uimp kV46
Isolation CompatibilityCompatible
Reverse Connection (Only When Using At 240 V AC or Less)-
External Dimensions
mm
a3654
b100
c68
ca90
Connection MethodPerfectly Suitable For front-surface type crimp terminals
IEC 35 mm Rail-Mounting AdapterStandard Equipment
Electrical Appliances and Material Safety ActCompliant
Overcurrent Tripping MethodThermal-magnetic
Trip ButtonAvailable
CE Mark-
CCC Certification-

*1: When using a 3-contact earth leakage breaker for 1 ø2 W, do not use the center contact connect the left and right contacts. When using for 1 ø3 W, connect the center contact to a neutral wire.
*2: Time delay type is 200 to 440 V for all models.
*3: The time delay type is fabricated at 20 A rated current or higher.
*4: Operation time for 0.45 s is 0.15 s to 0.45 s, for 1.0 s is 0.6 to 1.0 s, and for 2.0 s is 1.2 to 2.0 s.
*5: 2-contact product JIS C 8201-2-2 Ann. 1 Ann. 2 240 V AC breaking capacity is the same as 230 V AC.

External Dimensions

External dimensions

Variable Voltage Range in Which Electrical Leakage Protection Function Can Operate

Rated VoltageApplicable Circuit VoltageVariable Voltage Range in Which Electrical Leakage Protection Function Can Operate
100 to 240 V100, 110, 200, 220, 230, 240 V80 to 264 V
100 to 440 V100, 110, 200, 220, 240, 254, 265, 380, 400, 415, 440 V80 to 484 V
200 to 440 V200, 220, 240, 254, 265, 380, 400, 415, 440 V160 to 484 V
Part Number
NV63-CVF 2P 15A 100-240V 30MA
NV63-CVF 2P 20A 100-240V 30MA
NV63-CVF 2P 30A 100-240V 30MA
NV63-CVF 2P 50A 100-240V 30MA
NV63-CVF 2P 50A AC100-240V 30MA F
NV63-CVF 3P 15A 100-440V 30MA
NV63-CVF 3P 20A AC100-440V 30MA F
NV63-CVF 3P 20A AC100-440V 100MA F
NV63-CVF 3P 30A 100-440V 30MA
NV63-CVF 3P 30A AC100-440V 100MA F
NV63-CVF 3P 40A 100-440V 30MA
NV63-CVF 3P 40A AC100-440V 30MA F
NV63-CVF 3P 50A 100-440V 30MA
NV63-CVF 3P 50A AC100-440V 100MA F
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRated block capacity AC 400 V
(kA)
Number of Poles Rated Operating Voltage
(V)
Rated Current
(A)
rate sensitivity current
(mA)
Dimension width
(mm)
Type Type Features Type Specifications Power supply connection method Load side connection method

2,605,170 IDR

1 Piece(s) 13 Day(s) -2AC100-240153036-Economic productHarmonic/surge type--Screw terminalScrew terminal

2,605,170 IDR

1 Piece(s) Quote -2AC 100–240203036---Economical ProductsHigh Harmonics/Surge Compatible Table--

2,605,170 IDR

1 Piece(s) Quote -2AC100-240303036-Economic productHarmonic/surge type--Screw terminalScrew terminal

2,605,170 IDR

1 Piece(s) Quote -2AC 100–240503036---Economical ProductsHigh Harmonics/Surge Compatible Table--

-

1 Piece(s) Quote -2AC 100–240503036---Economical ProductsHigh Harmonics/Surge Compatible Table--

3,045,670 IDR

1 Piece(s) Quote 53AC100-440153054Economical product---Harmonic / surge compatible type--

3,045,670 IDR

1 Piece(s) Quote 53AC100 to 440203054---Economical ProductsHigh Harmonics/Surge Compatible Table--

3,045,670 IDR

1 Piece(s) Quote 53AC100 to 4402010054---Economical ProductsHigh Harmonics/Surge Compatible Table--

3,045,670 IDR

1 Piece(s) Quote 53AC100-440303054Economical product---Harmonic / surge compatible type--

3,045,670 IDR

1 Piece(s) Quote 53AC100 to 4403010054---Economical ProductsHigh Harmonics/Surge Compatible Table--

3,045,670 IDR

1 Piece(s) Same day 53AC100 to 440403054---Economical ProductsHigh Harmonics/Surge Compatible Table--

-

1 Piece(s) Quote 53AC100 to 440403054---Economical ProductsHigh Harmonics/Surge Compatible Table--

-

1 Piece(s) Quote 53AC100 to 440503054---Economical ProductsHigh Harmonics/Surge Compatible Table--

3,045,670 IDR

1 Piece(s) Quote 53AC100 to 4405010054---Economical ProductsHigh Harmonics/Surge Compatible Table--

Loading...

  1. 1
 

Basic Information

Ampere frame AF 50AF Rated block capacity AC 100 V(kA) 7.5 Rated block capacity AC 200 V(kA) 7.5
Mounting Method DIN/Screw retention Representative Standard PSE Dimension height(mm) 100
Dimension depth(mm) 90 Connection Method Surface form

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:021-8990-4102 / FAX:021-8990-5803
8:30am - 5:30pm (Monday - Friday)