Magnetic Contact Contactors B/BD-N Series

Magnetic Contact Contactors B/BD-N Series

The main circuit contact is a B-contact (always closed), applicable for switching motor controls and electric power circuits.

Part Number

Configured Part Number is shown.

MS-N Series Main Circuit B Contact Type AC Operation Type Electromagnetic Contactor Features

  • External dimensions and mounting surface area are greatly decreased compared to the conventional product, making for a small size and saving space.
  • Uses AC operation DC excitation method electromagnet.
  • Fully prevents noise.
  • Wide shared rated coil (nominal 200 V AC: rated 200 to 240 V AC 50/60 Hz).
  • Built-in surge absorbing function.
  • Greatly reduced power consumption.
  • Can be used with live part protection cover UN-CV / CZ□ type.
  • Twin contacts with high contact reliability are used as the auxiliary contact, and are applicable to a 20 V 5 mA load.
  • The material name used is displayed on major plastic parts, improving environmental compliance.
  • Main circuit inter-phase barrier is standard equipment, which improves safety.

MS-N Series Main Circuit B Contact Type AC Operation Type Electromagnetic Contactor Specifications

Rating / Performance

Operation MethodType NameMain Contact ConfigurationDC Rated Operating Current [A]Open Thermal Current
Ith[A]
Auxiliary Contact Configuration
DC Motor Load
(DC2, DC4 Class)
DC Resistance Load
(DC1 Class)
100 V To 110 V200 V To 220 V100 V To 110 V200 V To 220 V
AC OperationB-N201a2b, 3b8 (15)1 (5)15 (20)5 (10)252a
B-N6520 (50)3 (20)30 (65)10 (30)802a2b
B-N1001a2b3034020120
DC OperationBD-N201a2b81155252a
BD-N652033010802a2b
BD-N1003034020120
  • Note 1: DC rating is for when a 2-contact in-line is used. The value in ( ) is for when a 3-contact in-line is used.
  • Note 2: Electrical durability 500,000 times, mechanical durability 5,000,000 times, switching frequency 1,200 times/hour.
  • Note 3: When applying main circuit contact to AC, you can use the table below.
Operation MethodType NameMain Contact ConfigurationAC Rated Operating Current [A]
b-Contacta-Contact
Three-Phase2-Contact In-Line Single-Phase1-Contact Single-Phase1-Contact Single-Phase
200 V To 220 V380 V To 440 V200 V To 220 V200 V To 220 V200 V To 220 V
AC OperationB-N201a2b, 3b1813181818
B-N655035505050
B-N1001a2b8055808080
DC OperationBD-N201a2b1813181818
BD-N655035505050
BD-N1008055808080
 Closing, interruption role conditions / switching durabilityClosing only, no break / 500,000 timesClosing, break 500,000 timesClosing only, no break / 500,000 timesClosing, break 500,000 times

Note 1. Switching durability is the value when switching closing rated operating current × 6, or break rated operating current × 1, or when switching without interruption.

Characteristics

Type NameInput [VA]Power Consumption
[W]
Operating Voltage [V]Coil Current
[mA]
Operating Time [ms]
InstantaneousConstantOperationOpenCoil ON → Main b OFFCoil OFF → Main b ON
B-N2090154.0125 to 15575 to 110607 to 1513 to 25
B-N65210232.8110 to 14050 to 1008512 to 2845 to 105
B-N100270242.9110 to 14060 to 13010020 to 25110 to 130
BD-N20-950 to 6510 to 309038 to 5210 to 23
BD-N65-2455 to 6512 to 3024068 to 9213 to 29
BD-N100-3150 to 6512 to 30310104 to 15630 to 70
  • Note 1: The table above indicates the guideline values of characteristics when using a 200 V AC coil during AC operation (B-N□), and when using 100 V DC during DC operation (BD-N□).
  • Note 2: Operating voltage is 20°C cold state, for both AC operation (at 60 Hz) and DC operation. For coils other than 200 V AC and 100 V DC, purchase approximately proportional to the voltage.
  • Note 3: Input and power consumption are shown as average values. Stays nearly the same even when using coils other than 200 V AC or 100 V DC.
  • Note 4: Coil current is the average value when applying 220 V 60 Hz during AC operation, and when applying 100 V DC. When using a coil other than the 200 V AC coil, divide the constant input by the coil voltage to find the coil. When using a coil other than the 100 V DC coil, divide the power consumption by the coil voltage.
  • Note 5: Operating time is the value when applying 220 V 60 Hz during AC operation, and 100 V DC during DC operation. Stays nearly the same even when using coils other than 200 V AC or 100 V DC.
Part Number
B-N65 AC100V
B-N65 AC200V
B-N100 AC100V
BD-N65 DC12V
BD-N65 DC24V
BD-N100 DC24V
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipCoil rated voltage
(V)
Dimension length
(mm)
Dimension width
(mm)
Dimension thickness
(mm)
Specifications Uses Rated Alternating Current b Contact, Triple Phase 200 to 220 V AC
(A)
Uses Rated Alternating Current b Contact, Triple Phase 380 to 440V AC
(A)

2,974,167 IDR

1 Piece(s) Quote AC100124100127Alternating Current Operation5035

-

1 Piece(s) Quote AC200124100127Alternating Current Operation5035

-

1 Piece(s) Quote AC100150100137Alternating Current Operation8055

-

1 Piece(s) Quote DC12134100158Direct current operation5035

-

1 Piece(s) Quote DC24134100158Direct current operation5035

-

1 Piece(s) Quote DC24150102162Direct current operation8055

Loading...

  1. 1

Basic Information

Operating Method Irreversible type Number of Poles 3 Auxiliary Contact 2a2b
Equipment Name Main circuit B contact type electromagnetic contact device