Magnetic Contactors DU-N Series (DU-N260 AC100V)

Part Number

Configured Part Number is shown.

DU-N260 AC100V

MS-N Series AC Operation Electromagnetic Contactor For Direct Current Features

  • External dimensions and mounting surface area are greatly decreased compared to the conventional product, making for a small size and saving space.
  • Uses AC operation DC excitation method electromagnet.
  • Fully prevents noise.
  • Wide shared rated coil (nominal 200 V AC: rated 200 to 240 V AC 50/60 Hz).
  • Built-in surge absorbing function.
  • Greatly reduces power consumption (DU-N30: 2.2 W, DU-N120: 2.9 W).
  • Conforms to finger protection. Compatible with live part protection cover unit UN-CZ□ type, used for the MS-N series.
  • Twin contacts with high contact reliability are used as the auxiliary contact, and are compatible with 20 V DC 5 mA.
  • Compatible with auxiliary power contactor UN-AX□ type, used for the MS-N series.
  • The material name used is displayed on major plastic parts, improving environmental compliance.
  • Uses thermoplastic resin around terminals, enhancing the strength of plastic parts.

MS-N Series AC Operation Electromagnetic Contactor For Direct Current Specifications

Rating

Operation MethodType NameMain Contact
Configuration
Main Contact
In-Line Connection
Rated Operating Current [A]Rated Capacity [kW]Open Thermal
Current
Ith [A]
Rated Insulation
Voltage
Auxiliary Contact
Configuration
Variable Speed Motor Control: a Contact
Dynamic Brake: b Contact
Common DC Motor
(DC2, DC4 Class)
Common DC Motor
(DC2, DC4 Class)
110 V DC220 V DC440 V DC110 V DC220 V DC440 V DC110 V DC220 V DC440 V DC
AC OperationDU-N302a1ba-ContactSingle contact4040153020-2.23.7-60660 V2a2b
2-contact5050404030203.75.57.5
b contact single contact120 *1120 *1120 *12015-1.52.2-50
DU-N60a-ContactSingle contact8080306040-5.57.5-120
2-contact9090808060407.51115
b contact single contact240 *1240 *1240 *14030-3.75.5-100
DU-N120a-ContactSingle contact1601606012080-1115-160
2-contact16016016016012080152230
b contact single contact480 *1480 *1480 *18060-7.511-
DU-N180a-ContactSingle contact26026090180120-1522-270
2-contact260260260240180120223545
b contact single contact720 *1720 *1720 *110075-7.511-260
DU-N260a-ContactSingle contact360360130260175-2230-360
2-contact360360360350260175304555
b contact single contact1,040 *11,040 *11,040 *1150100-1118.5-
  • Note 1: The role of the a-contact for variable motor control is double-loading / non-voltage closing, and the role of the b-contact for dynamic brake contact is 1 × loading / non-voltage closing.
  • Note 2: A common DC motor is compatible with motor load for DC2 class (shunt motor start/stop) and DC4 class (series-wound motor start/stop) from JEM1038.
  • Note 3: The *1 allowed energization time is 30 seconds. When using for inching, use the rated operating current for common DC motors.

Performance

Type NameMain Contact
In-Line Connection
Breaking Current Capacity [A] *1Closing Current
Capacity [A]
Switching Frequency
[Times/Hour]
Switching Durability [10,000 Times]Performance
110 V DC220 V DC440 V DCMechanicalElectrical
DU-N30b contact single contact8060-1601,20025050DC2,1/2-1
DU-N60b contact single contact160120-320
DU-N120b contact single contact320240-640
DU-N180b contact single contact400300-960
DU-N260b contact single contact600400-1,400

Note 1. *1 time constant L/R = 15 ms, break count 25 times.

Characteristics

Type NameInput [VA]Power Consumption
[W]
Operating Voltage [V]Coil Current
[mA]
Operating Time [ms]
InstantaneousConstantOperationOpenCoil ON > Main a ONCoil ON > Main b OFFCoil OFF > Main a OFFCoil OFF > Main b ON
DU-N30115202.2133576712 to 1510 to 1366 to 7265 to 76
DU-N60270242.91126810020 to 2317 to 2075 to 10378 to 108
DU-N120270242.91257610025 to 2720 to 2275 to 10380 to 110
DU-N180440404.21097616532 to 3424 to 2685 to 10590 to 140
DU-N260440506.11125820037 to 3929 to 31100 to 130105 to 140
  • Note 1: The table above indicates the guideline values of characteristics when using a 200 V AC coil during AC operation (DU-N□).
  • Note 2: Operating voltage is the average value during AC operation (at 60 Hz). For coils other than 200 V AC, purchase approximately proportional to the voltage.
  • Note 3: Input and power consumption are shown as average values. Nearly identical even for coils other than 200 V AC.
  • Note 4: Coil current is the average value when applying 220 V 60 Hz during AC operation. When using a coil other than the 200 V AC coil, divide the constant input by the coil voltage to find the coil.
  • Note 5: Operating time is the value when applying 220 V 60 Hz during AC current. Nearly identical even for coils other than 200 V AC.
Part Number
DU-N260 AC100V
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipDimension length
(mm)
Dimension width
(mm)
Dimension thickness
(mm)
Rated current used DC 110 V variable speed motor control: for 2-pole
(A)
Rated current used DC 220 V variable speed motor control: for 2-pole
(A)

-

1 Piece(s) Quote 243163195360360

Loading...

  1. 1

Basic Information

Operating Method Irreversible type Coil rated voltage(V) AC100 Number of Poles 3
Auxiliary Contact 2a2b Equipment Name Electromagnetic contact device for direct current Specifications Alternating Current Operation

Please check the type/dimensions/specifications of the part DU-N260 AC100V in the Magnetic Contactors DU-N Series series.

Products like this...

Part Number
DU-N30 AC100V
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipDimension length
(mm)
Dimension width
(mm)
Dimension thickness
(mm)
Rated current used DC 110 V variable speed motor control: for 2-pole
(A)
Rated current used DC 220 V variable speed motor control: for 2-pole
(A)

-

1 Piece(s) Quote 106881065050