Earth Leakage Circuit Breakers (ELCB) NV-CVF Series (NV125-CVF 3P 125A AC100-440V 30MA F)

Part Number

Configured Part Number is shown.

NV125-CVF 3P 125A AC100-440V 30MA F

NV63-CVF Characteristics And External Shape

Type NameNV63-CVF
Rated Current In
Standard ambient temperature 40°C
A60
Number of contacts23
Phase wire modelø 1, 2 W1 ø 2 W,
3 ø 3 W,
1 ø 3 W
Rated operating voltage Ue VAC100-
240
100-
440
High-speed

type
Rated sensitivity current mA3030
100
200
500
Maximum operating time sat I △n0.1
at 5I △n0.04
Time-delay

type
Rated sensitivity current mA-
Maximum operating time s-
Inertia dead time s or more-
Electrical leakage display methodDisplay window
Rated
short
circuit
breaking
capacity
kA


JIS C 8201-2-2 Ann. 1
JIS C 8201-2-2 Ann. 2
IEC 60947-2 2nd. ed.
(Icu/Ics)
AC440 V
-2.5/2.5
415 V
-5/5
400 V
-5/5
230 V
7.5/7.5
200 V
7.5/7.5
100 V7.5/7.5

NV63-CVF Dimensional Outline Drawing (Front Surface Type)

Front Surface Type

Note: Wires cannot be connected directly. Motor breaker is 3-contact only.

NV125-CVF Characteristics And External Shape

Type NameNV125-CVF
Rated current In (Note 2)
Standard ambient temperature 40°C
A60 75 100125
Number of contacts33
Phase wire model⌀3 3 W,
⌀1 3 W, ⌀1 2 W
⌀3 3 W,
⌀1 3 W, ⌀1 2 W
Rated operating voltage Ue V (Note 1)AC100-440100-440
High-speed

type
Rated sensitivity current mA30
100/200/500 switch
30
100/200/500 switch
Maximum operating time sat I △n0.10.1
at 5I △n0.040.04
Time-delay

type
Rated sensitivity current mA(100/200/500 switch)(100/200/500 switch)
Maximum operating time s(0.45/1.0/2.0 switch)(0.45/1.0/2.0 switch)
Inertia dead time s or more(0.1/0.5/1.0)(0.1/0.5/1.0)
Electrical leakage display methodMechanical button
Rated
short
circuit
breaking
capacity
kA


JIS C 8201-2-2 Ann. 1
JIS C 8201-2-2 Ann. 2
IEC 60947-2 2nd
(Icu/Ics)
AC440 V
10/5
10/5
415 V
10/5
10/5
400 V
10/5
10/5
230 V
30/15
30/15
200 V
30/15
30/15
100 V30/1530/15

Note 1: The time-delay type rated operating voltage is 200-440 V.
Note 2: The time-delay type is fabricated at 20 A or higher.

NV125-CVF Dimensional Outline Drawing (Front Surface Type)

Front Surface Type
  • * See the catalog for details on products.
Part Number
NV125-CVF 3P 125A AC100-440V 30MA F
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipAmpere frame AF Rated block capacity AC 100 V
(kA)
Rated block capacity AC 200 V
(kA)
Rated block capacity AC 400 V
(kA)
Rated Current
(A)
rate sensitivity current
(mA)
Representative Standard Dimension height
(mm)
Dimension width
(mm)
Rated block capacity, voltages except VAC 100/200/400, VDC 250

7,450,330 IDR

1 Piece(s) Quote [100AF to 199AF] 125AF30301012530-13075-

Loading...

  1. 1
 

Basic Information

Number of Poles 3 Rated Operating Voltage(V) AC100 to 440 Mounting Method DIN/Screw retention
Dimension depth(mm) 90 Connection Method Surface form Type Economical Products
Specifications High Harmonics/Surge Compatible Table

Please check the type/dimensions/specifications of the part NV125-CVF 3P 125A AC100-440V 30MA F in the Earth Leakage Circuit Breakers (ELCB) NV-CVF Series series.

Products like this...

Part Number
NV125-CVF 3P 100A 100.200.500MA
NV125-CVF 3P 100A 30MA
NV125-CVF 3P 125A 100-440V 1.2.500MA
NV125-CVF 3P 60A 100-440V 1.2.500MA
NV125-CVF 3P 60A AC100-440V 30MA F
NV125-CVF 3P 75A 100-440V 1.2.500MA
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipAmpere frame AF Rated block capacity AC 100 V
(kA)
Rated block capacity AC 200 V
(kA)
Rated block capacity AC 400 V
(kA)
Rated Current
(A)
rate sensitivity current
(mA)
Representative Standard Dimension height
(mm)
Dimension width
(mm)
Rated block capacity, voltages except VAC 100/200/400, VDC 250

7,450,330 IDR

1 Piece(s) Quote [100AF to 199AF] 125AF303010100100· 200· 500 switchPSE13075Available

-

1 Piece(s) Quote [100AF to 199AF] 125AF30301010030PSE13075Available

-

1 Piece(s) Quote [100AF to 199AF] 125AF303010125100· 200· 500 switch-13075Available

-

1 Piece(s) Quote [100AF to 199AF] 125AF30301060100· 200· 500 switchPSE13075Available

-

1 Piece(s) Quote 60AF3030106030PSE13075-

-

1 Piece(s) Quote [100AF to 199AF] 125AF30301075100· 200· 500 switchPSE13075Available

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:021-8990-4102 / FAX:021-8990-5803
8:30am - 5:30pm (Monday - Friday)