(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Penghentian penjualan kategori produk pneumatik Seri Ekonomi (E-series). Info Detail
    Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series (HRS012-A-20-BGMT)

Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series HRS012-A-20-BGMT

[Features]
· With a high temperature stability of ±0.1°C due to a precise temperature control method that uses an expansion valve and a temperature sensor.
· With a compact tank.
· Power supply: Single-phase 200 to 230 V AC.
· Set temperature range: 5 to 40°C.
· HRS-0□□-A: Air-cooled refrigeration type.
· HRS-0□□-W: Water-cooled refrigeration type.

(i)Caution

  • Webpages for products currently without individual pages on this site will be released on an ad-hoc basis.
  • Refer to the manufacturer's catalog for specification and material details.
  • Product images may be representative images. Refer to the manufacturer's catalog for shape details.

PDF

Part Number

Configured Part Number is shown.

HRS012-A-20-BGMT

Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series Specifications

Air-Cooled Refrigeration Type External Appearance / Specifications

HRS Series Air-Cooled Refrigeration Type external appearance

HRS Series Air-Cooled Refrigeration Type external appearance

ModelHRS012-A□-20HRS018-A□-20HRS024-A□-20HRS030-A□-20HRS050-A□-20HRS060-A□-20
Cooling MethodAir-cooled refrigeration type
RefrigerantR407C (HFC)R410A (HFC)
Refrigerant Charge (kg)0.350.360.360.570.650.85
Control MethodPID control
Ambient Operating Temperature / Humidity / Altitude*1 *12Temperature: 5 to 40°C, High-temperature environment specification (optional): 5 to 45°C, Humidity: 30 to 70%, Altitude: less than 3,000 m
Circulating Fluid SystemCirculating Fluid*2Clear water, 15% ethylene glycol aqueous solution*4
Set Temperature Range*1 (°C)5 to 40
Cooling Capacity*3 (50/60 Hz) (W)1,100/1,3001,700/1,9002,100/2,4002,600/3,2004,700/5,1004,900/5,900
Heating Capacity*3 (50/60 Hz) (W)530/650600/6401,100/1,4001,000/1,300
Temperature Stability*5 (°C)±0.1
PumpRated Flow Rate*6 *7 (50/60 Hz) (L/min)7 (0.13 MPa) / 7 (0.18 MPa)23 (0.24 MPa) / 28 (0.32 MPa)23 (0.21 MPa) / 28 (0.29 MPa)
Maximum Flow Rate (50/60 Hz) (L/min)27/2934/4031/4229/38
Maximum Pump Head (50/60 Hz) (m)14/1950
Output (W)200550
Tank Capacity (L)Approx. 5
Pipe Connection Port DiameterRc 1/2
Fluid Contacting Parts MaterialStainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC
Electrical SystemsPower SupplySingle-phase 200 to 230 V AC (50/60 Hz)
Allowable voltage variation ±10%
Circuit Protector (A)102030
Compatible Earth Leakage Circuit Breaker Capacity*8 (A)102030
Rated Operating Current (A)4.6/5.14.7/5.25.1/5.95.2/6.08/118.9/11.5
Rated Power Consumption*3 (50/60 Hz) (kVA)0.9/1.00.9/1.01.0/1.21.0/1.21.7/2.21.8/2.3
Noise Level*9 (50/60 Hz) (dB)60/6162/6565/6866/68
AccessoriesPipe fitting (for drain outlet) 1 pc.*11, Input/output signal connector 1 pc., Power supply connector 1 pc.*11
Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*11
Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc.
Power cable must be purchased separately or provided by the user.
Weight*10 (kg)43476973

*Some values differ from the standard specifications due to optional features. See the catalog for details.

*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc. Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11: Not included with the HRS050/060.
*12: For altitudes above 1,000 m, please refer to "*For altitudes above 1,000 m" in Section 14 "Operating Environment and Storage Environment," on p. 64 of the catalog.

Water-Cooled Refrigeration Type External Appearance / Specifications

HRS Series Water-Cooled Refrigeration Type external appearance

HRS Series Water-Cooled Refrigeration Type external appearance

ModelHRS012-W□-20HRS018-W□-20HRS024-W□-20HRS030-W□-20HRS050-W□-20HRS060-W□-20
Cooling MethodWater-cooled refrigeration type
RefrigerantR407C (HFC)R410A (HFC)
Refrigerant Charge (kg)0.30.310.310.50.650.75
Control MethodPID control
Ambient Operating Temperature / Humidity / Altitude*1Temperature: 5 to 40°C, Humidity: 30 to 70%, Altitude: Less than 3,000 m
Circulating Fluid SystemCirculating Fluid*2Clear water, 15% ethylene glycol aqueous solution*4
Set Temperature Range*1 (°C)5 to 40
Cooling Capacity*3 (50/60 Hz) (W)1,100/1,3001,700/1,9002,100/2,4002,600/3,2004,700/5,1004,900/5,900
Heating Capacity*3 (50/60 Hz) (W)530/650400/6001,000/1,300
Temperature Stability*5 (°C)±0.1
PumpRated Flow Rate*6 *7 (50/60 Hz) (L/min)7 (0.13 MPa) / 7 (0.18 MPa)23 (0.24 MPa) / 28 (0.32 MPa)23 (0.21 MPa) / 28 (0.29 MPa)
Maximum Flow Rate (50/60 Hz) (L/min)27/2934/4031/4229/38
Maximum Pump Head (50/60 Hz) (m)14/1950
Output (W)200550
Tank Capacity (L)Approx. 5
Pipe Connection Port DiameterRc 1/2
Fluid Contacting Parts MaterialStainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC
Heat-Dissipating Water SystemTemperature Range (°C)5 to 40
Pressure Range (MPa)0.3 to 0.5
Required Flow Rate*11 (50/60 Hz) (L/min)81214151617
Inlet-Outlet Pressure Differential of Heat-Dissipating Water (MPa)0.3 or more
Pipe Connection Port DiameterRc3/8Rc 1/2
Fluid Contacting Parts MaterialStainless steel, copper (heat exchanger brazing), bronze, synthetic rubber
Electrical SystemsPower SupplySingle-phase 200 to 230 V AC (50/60 Hz)
Allowable voltage variation ±10%
Circuit Protector (A)1020
Compatible Earth Leakage Circuit Breaker Capacity*8 (A)1020
Rated Operating Current (A)4.6/5.14.7/5.25.1/5.95.2/6.07.6/107.6/10.4
Rated Power Consumption Note 3) (50/60 Hz) kVA0.9/1.00.9/1.01.0/1.21.0/1.21.5/2.01.5/2.1
Noise Level*9 (50/60 Hz) (dB)60/6162/6565/6866/68
AccessoriesPipe fitting (for drain outlet) 1 pc.*12, Input/output signal connector 1 pc., Power supply connector 1 pc.*12
Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*12
Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc.
Power cable must be purchased separately or provided by the user.
Weight*10 (kg)434667

*Some values differ from the standard specifications due to optional features. See the catalog for details.

*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water, 5. Heat-dissipating water temperature: 25°C. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc.
Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].)
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11 Required flow rate when the circulating fluid temperature is 20°C, the circulating fluid is at the rated flow rate, the heat-dissipating fluid is 25°C and the listed cooling capacity load is applied.
*12: Not included with the HRS050/060.

Pump Capacity

HRS012/018-A/W-10 (single-phase 100/115 V AC) pump capacity

HRS012/018-A/W-10 (single-phase 100/115 V AC) pump capacity

HRS-012/018/024-A/W-20 (single-phase 200 to 230 V AC) pump capacity

HRS-012/018/024-A/W-20 (single-phase 200 to 230 V AC) pump capacity

Mechanical seal details

Mechanical seal details

Notes

*The pump used in the Thermo-Chiller HRS050/060 Series uses a mechanical seal with a fixed ring and a rotating ring in the shaft seal. If foreign matter enters the gap in the seal, it could cause issues such as seal leakage, pump lock, etc., so it is highly recommended that a particle filter is installed on the chiller return piping.

Dimensions

 

(Unit: mm)

 

HRS012/018/024 dimensions/diagram

HRS012/018/024 dimensions/diagram

  1. *1: A power supply cable is not included. (Power supply connectors are included.)
  2. *2: Conversion fitting (R 3/8 male thread) is included.
HRS030-A-20 dimensions/diagram

HRS030-A-20 dimensions/diagram

  1. *1: A power supply cable is not included. (Power supply connectors are included.)
  2. *2: Conversion fitting (R 3/8 male thread) is included.
HRS030-W-20 dimensions/diagram

HRS030-W-20 dimensions/diagram

  1. *1: A power supply cable is not included. (Power supply connectors are included.)
  2. *2: Conversion fitting (R 3/8 male thread) is included.
HRS050/060-A dimensions/diagram

HRS050/060-A dimensions/diagram

HRS050/060-W dimensions/diagram

HRS050/060-W dimensions/diagram

  • *For information other than the above, please refer to the catalog.
  • *Product pictures are representative images.
Part Number
HRS012-A-20-BGMT
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipType Cooling Method Cooling capacity Piping thread type Optional specifications Cooling method Power Supply Specification

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcWith earth leakage circuit breaker / High-temperature environment specification / Compatible with deionized water (pure water) piping / High pump head specificationAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

Loading...

  1. 1

Please check the type/dimensions/specifications of the part HRS012-A-20-BGMT in the Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series series.

Products like this...

Part Number
HRS012-A-20
HRS012-A-20-BJW
HRS012-A-20-BW
HRS012-A-20-MW
HRS012-A-20-TW
HRS012-A-20-W
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipType Cooling Method Cooling capacity Piping thread type Optional specifications Cooling method Power Supply Specification

85,164,175 IDR

1 Piece(s) 20 Day(s) Thermo-ChillerAir-Cooling1,100/1,300 W (50/60 Hz)RcNone--

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcWith earth leakage circuit breaker / with automatic water supply / SI unit onlyAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcWith earth leakage circuit breaker / SI unit onlyAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcFor deionized water (pure water) piping / SI unit onlyAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcHigh head pump specifications / SI unit onlyAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

-

1 Piece(s) 15 Day(s) --1,100/1,300 W (50/60 Hz)RcSI unit fixedAir-cooled refrigeration typeSingle-phase 200 to 230 V AC (50/60 Hz)

Tech Support